Section 8 Parameters
CH
Function
Setting
CH
PV Tracking
Function
Setting
8-100
alfa
• This parameter is normally used at the default value.
• This parameter sets the 2-PID constant .
Setting range
0.00 to 1.00
pvtr
• This parameter is used so have the fixed SP track the PV when in
Manual Mode.
• The setting prevents abrupt changes in the MV when switching from
Manual Mode to Auto Mode.
SP
PV
Auto mode
Setting range
off: Disabled
on: Enabled
If an input error occurs during PV tracking, the fixed SP will change to
the upper limit of the sensor setting range.
Unit
Default value
0.65
Manual mode
Auto mode
Time
Unit
Default value
off: Disabled
l.exc
l.exc