Section 3 Typical Control Examples
Control Initial Setting Level
o1-t
Output 1
Type
0
l.1
mode
Control Mode
0
l.1
Direct/Reverse
oreV
Operation
or-r
l.1
PV Start
pust
sp
l.1
Move to Advanced
amoV
Function Setting
Level
0
-169
l.0
Expansion control setting level
p-on
cont
l.exc
eset
End Condition
rst
cont
l.exc
Adjustment level
at
off
l.adj
Control Period
cp
( Heating )
20.0
2.0
D
l.adj
3-4
3. Press the L Key for less than 1 second to move from the Input Initial
Setting Level to the Control Initial Setting Level. o1-t (Output 1 Type) will
be displayed. Make sure that the set value is 0 (Pulse Voltage Output).
4. Press the M Key repeatedly to select mode (Control Mode). Make sure
that the setting is 0 (Standard Control).
5. Press the M Key to select orev (Direct/Reverse Operation). Make sure
that the setting is or-r (Reverse Operation).
6. Press the M Key repeatedly to select pvst (PV Start). Make sure that the
setting is sp (SP Start).
7. Press the L Key for less than 1 second to move from the Control Initial
Setting Level to the Input Initial Setting Level and then press the M Key
repeated to select anov (Move to Advanced Function Setting Level). Press
the D Key and set the password to -169 to move to Advanced Function
Setting Level.
8. Press the L Key or less than 1 second to move from the Advanced
Function Setting Level to the Expansion Control Setting Level.
9. Press the M Key to select eset (End Condition). Press the U Key to
select the setting cont (Continue).
10. Press the L Key twice for at least 1 second to return to the Operation
Level, and then press the L Key for less than 1 second to move from the
Operation Level to the Adjustment Level.
11. Press the M Key repeatedly to select cp (Control Period (Heating)), and
then press the D Key to select 2.0.