CH
MV at Reset (Standard/Heating/Cooling)
MV at PV Error
Function
Setting
Reference
Reference
mv-r
mv-e
• On a Standard Control Model, the MV at Reset parameter is set to
the MV to output when operation is stopped. On a Position-propor-
tional Control Model, the MV at Reset parameter is set to the
position when operation is stopped (Closed/Hold/Open). If the
Operation at Reset parameter is set to "Fixed Control", the MV
cannot be used.
• On a Standard Control Model, the MV at PV Error parameter is set
to the MV to output when an error occurs. On a Position-proportional
Control Model, the MV at Reset parameter is set to the position
when an error occurs (Closed/Hold/Open).
• Standard Control Model
Control method
Standard
5.0 to 105.0
Heating/Cooling
105.0 to 105.0
A negative value is set for the cooling MV for heating/cooling control.
• Position-proportional Control Model
Control method
Position
1: Closed,
Proportional
0: Hold, 1: Open
● Related Information
4.12 Starting and Stopping Operation (P. 4-41)
8.5 Adjustment Level (l.adj)
Setting range
Unit
%
%
Setting range
Unit
l.adj
Default value
0.0
0.0
Default value
0: Hold