■ AT execute

Command
Response

■ AT cancel

Command
6.9 Commands and responses (Communication/CompoWay/F)
Instruction
Related
MRC
SRC
code
information
"30"
"05"
"03"
Related
information
Ch
00: Currently selected PID Set No.
"00" to "08"
1
01 to 08: Specifies PID Set No. 1 to 8
10: Currently selected PID Set No.
"10" to "18"
2
11 to 18: Specifies PID Set No. 1 to 8
20: Currently selected PID Set No.
"20" to "28"
3
21 to 28: Specifies PID Set No. 1 to 8
30: Currently selected PID Set No.
"30" to "38"
4
31 to 38: Specifies PID Set No. 1 to 8
F0: Currently selected PID Set No.
"F0" to "F8"
All
F1 to F8: Specifies PID Set No. 1 to 8
This command runs AT. On the E5AR/ER, the PID Set No. must be
specified when running AT.
To specify the currently selected PID Set No. (the PID set currently
used for operation), set the lower byte of the related information to "0".
This command is used in setting area 0. If used in setting area 1, an
operation error will result. An operation error will also result in the
following situations:
• "Run/Stop" of the specified channel is set to "Stop".
• "Auto / Manual" of the specified channel is set to "Manual".
To use this command, "Write via communication" must be enabled
using the "Write via communication" operation command.
MRC
SRC
Response code
"30"
"05"
"0000"
Response codes: The above indicates a normal end. For the response
codes, see "6.7 Operation commands (Communication/CompoWay/
F)" (P.6-11).
Instruction
Related
MRC
SRC
code
information
"30"
"05"
"0A"
Related
information
Ch
"00"
1
"10"
2
"20"
3
"30"
4
"F0"
All
Description
Command
Description
Operation
Stops AT
Stops AT
Stops AT
Stops AT
Stops AT
6-23