Chapter 3 Basic Operations
3.6

Verifying PID Constants (AT and manual settings)

■ AT (auto-tuning)

● Explanation
3-10
When using auto-tuning, the program will force modifications in operation
volume to calculate the set point's optimal PID parameter, and calculate the
unique automatic settings of the controlled object (the "limit cycle method").
Select "on: Execute AT" execute AT (auto-tuning), select "off: Cancel AT"
to cancel AT (auto-tuning). When AT is finished, "on" will fall-back to "off"
automatically.
In the "adjustment level", the "proportional band (P)", "integral time (I)", and
"derivative time (D)" parameters indicate the AT (auto-tuning) results.
Adjustment Level
c
p
8.0
l. adj
i
233
l. adj
d
40
l. adj
When the "execute/cancel AT" parameter is set to "ON", AT (auto-tuning) is
activated. During AT execution, the "execute/cancel AT" parameter flashes on
the No. 1 display. When AT is finished, the "execute/cancel AT" parameter goes
off, and No. 1 display stops flashing.
Execute/cancel
AT
If while AT is executing you switch to the "operation level ", No. 2 display will flash
to indicate that AT is executing.
present value/
set point /
valve open percentage
When AT is executing, only the "communication writing", "run/stop" and
"execute/cancel AT" parameters may be changed. Other parameters may not be
changed.
Proportional Band
Integral Time
Derivative Time
at
at
off
on
l.adj
l.adj
When AT is executing
c
c
25
100
100.0
100.0
When AT is executing
No. 1 Display
No. 2 Display
25
100