Model Specifications (Three-Phase 200 V Class) - YASKAWA GA500 Maintenance & Troubleshooting

Industrial ac microdrive
Table of Contents

Advertisement

7.3 Model Specifications (Three-Phase 200 V Class)

7.3

Model Specifications (Three-Phase 200 V Class)

Model
Maximum Applicable Motor Output (kW)
Maximum Applicable Motor Output (HP)
Input
Rated Input Current (A)
Rated Output Capacity
*3
(kVA)
Rated Output Current
(A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage
Maximum Output Frequency
Measures for Harmonics DC reactor
Braking Device
Braking Transistor
EMC Filter
EMC Filter
IEC61800-3
Rated Voltage/Rated Frequency
Permitted Voltage Fluctuation
Power Supply
Permitted Frequency Fluctuation
Input Power (kVA)
*1
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output current of
the drive output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*3
The rated output capacity is calculated with a rated output voltage of 220 V.
266
Table 7.3 Ratings (Three-Phase 200 V Class)
2001
*1
HD
0.1
*2
ND
0.2
*1
HD
1/6
*2
ND
1/6
0.7
HD (AC)
HD (DC)
0.9
1.1
ND (AC)
1.3
ND (DC)
HD
0.3
ND
0.5
HD
0.8
ND
1.2
• HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is one
time each 10 minutes.
• ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is one
time each 10 minutes.
Note:
Derating can be necessary for applications that start and stop frequently.
HD: 10 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Three-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
• EZOLV: 120 Hz
• AOLV/PM: 270 Hz
• V/f, OLV, OLV/PM: 590 Hz
External options
Standard internal characteristics
Factory option
Models 2xxxE: Category C3 (Conducted emission)
• Three-phase AC power supply 200 V to 240 V at 50/60 Hz
• DC power supply 270 V to 340 V
-15% to +10%
±5%
HD
0.3
ND
0.5
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
2002
2004
0.2
0.2
0.4
0.75
1/4
1/2
1/4
3/4
1.5
2.9
1.8
3.6
1.9
3.9
2.3
4.8
0.6
1.1
0.7
1.3
1.6
3.0
1.9
3.5
0.7
1.3
1.2
1.8
2006
0.75
1.1
1
1.5
5.8
7.1
7.3
8.9
1.9
2.3
5.0
6
2.7
3.3

Advertisement

Table of Contents
loading

Table of Contents