Program:transient Triggers Commands - Pacific Power Source LMX Series Operation Manual

Programmable ac power source
Table of Contents

Advertisement

8.10.3 PROGram:TRANsient Triggers Commands

PROGram:TRANsient:TRIGger
:Input[?]
:OUTput[?]
8.10.3.1
PROGram:TRANsient
The following PROGram:TRANsient:TRIGger commands are available.
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Returned Data Format
Query Example
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Returned Data Format
Query Example
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
:IMMediate[?]
:AUTOrun[?]
PROGram:TRANsient:TRIGger:INput
When the trigger input is active, this command selects the trigger
input source mode as on or off. When ON, the external trigger input
is enabled.
[ 0 | OFF | 1 | ON ]
<b>
PROG:TRAN:TRIG:IN 1
PROGram:TRANsient:TRIGger:INput?
<b>
PROG:TRAN:TRIG:IN?
1
PROGram:TRANsient:TRIGger:INput:IMMediate <b>
When the trigger input is active, this command starts the transient
segments immediately after the trigger input is received, without
waiting for the zero crossing, as determined by the update phase
setting. Refer to SOURce:UPDATEPHase
[ 0 | OFF | 1 | ON ]
<b>
PROG:TRAN:TRIG:IN:IMM 1
PROGram:TRANsient:TRIGger:INput:IMMediate?
<b>
PROG:TRAN:TRIG:IN:IMM?
1