2.1.8 OUTPUT BANDWIDTH
The output bandwidth of the AMX-Series Power Source is listed below.
Full Power:
Small Signal:
(rated at 10% of full-scale output voltage)
2.1.9 LOAD TRANSIENT RESPONSE
Output load transient response for a 0-100% load induced step transient is approximately
5 μsec.
2.1.10 OUTPUT DC OFFSET
The DC offset present on the output of the AMX-Series Power Source is less than 10 mVDC
for the Models 105, 108, 112, 305, 308, 312, and 320-AMX; and less than 5 mVDC for the
Models 125, 140, 160, 345, 360, 390, and 3120-AMX.
2.1.11 OUTPUT PROTECTION
The output of the AMX-Series Power Source is protected through the use of electronic current
limiting. The output will automatically recover when the output fault is removed. Thermal
overload protection is also provided. Refer to paragraph 2.3.3 for details.
Note:
The programmable controller also provides programmable current
limit. Refer to the UPC-Series Operation Manual for details.
2.1.12 OUTPUT CONTROL CHARACTERISTICS
Output control characteristics, sync I/O signals and metering capabilities are determined by
the controller which is installed. Refer to the appropriate controller manual for details.
2.1.13 OUTPUT ISOLATION
The output of the AMX-Series is galvanically isolated from the chassis and input power.
Maximum allowable output Neutral to Chassis voltage is 150 VAC. (Refer to Paragraph
3.4.4 for special considerations when using transformer-coupled outputs.)
45
to
500 Hz (±0.10 db [± 1%])
20
to
5,000 Hz (±0.25 db [± 3%])
5
to
40,000 Hz (±3 db [±30%])
31
SECTION 2
SPECIFICATIONS