The mode can be set from the front panel or by using the following SCPI commands:
Transient start mode:
Output Relay mode:
Program Change mode:
The following specifications apply to the external trigger output:
Output Voltage @ 0.4 mA Logic Low Vout < 0.4 V
Max. Current
Output Impedance
Pulse Width
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
SECTION 7: Auxiliary I/OError! Reference source not found.
SYSTem:DIO:STROBE:TRANsient 0/1
PROGram:TRANsient:TRIGger:OUTput 0/1
SYSTem:DIO:STROBE:OUTPutstate 0/1
SYSTem:DIO:STROBE:SOURce 0/1
Log High Vout > 4.6 V
± 10 mA
100 Ω
190 us ± 10 us
2.0 msec ± 10 µs
Figure 7-6: Transient Trigger Output Pulse
Figure 7-7: Function Strobe Output Pulse
LMX SERIES™ OPERATION MANUAL
(alias)
For Transient Trigger mode
For OUTPutstate & SOURce
modes
Page 186 of 463