8.4.2

Frequency Measurement Commands

Query Format
Description
Returned Data Format
Query Example
8.4.3

Current Measurement Commands

Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
MEASure:FREQuency#?
Returns the fundamental frequency for the selected phase #. If no
phase number is specified, returns the reading for the last selected
phase. For frequency measurements, the phase reference is
irrelevant as all phase are at the same frequency.
<nr2>
MEAS:FREQ?
50.0000
MEASure:CURRent[:ACDC]#?
Returns the measured RMS current for the selected phase #. If no
phase number is specified, returns the reading for all phases.
<nr2>
MEAS:CURR:ACDC1?
21.1587
MEASure:CURRent:PEAK#[:ABSolute]?
Returns the measured peak current value for the selected phase #. If
no phase number is specified, returns the reading for all phases.
<nr2>
MEAS:CURR:PEAK?
45.5845, 47.3213, 48,2234
MEASure:CURRent:PEAK#[:ABSolute]:HOLD?
Returns the measured peak hold current value for the selected phase
#. If no phase number is specified, returns the reading for all phases.
This reading accumulates the highest recorded absolute peak current
until reset using the MEASure:CURRent:PEAK#:RESet command.
<nr2>
MEAS:CURR:PEAK:HOLD?
58.5845, 57.3213, 58,2234
MEASure:CURRent:PEAK#:MINimum?
Returns the lowest measured peak current value for the selected
phase #. If no phase number is specified, returns the reading for all
phases.
<nr2>
MEAS:CURR:PEAK:MIN?
1.0001, 0.8451, 0.4871