Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
MEASure:SPECTrum:VLL#:THD?
Same as "MEASure:SPECTrum:THD?" but selects Line to Line voltage
#.Returns Total Harmonic Distortion of the selected Line to Line
voltage.
<nr2>
MEAS:SPECT:VLL1:THD?
2.5600
MEASure:SPECTrum:CURRent#:THD?
Same as "MEAS:SPECTrum:THD?" but selects current and phase
#.Returns Total Harmonic Distortion of the selected phase currebt.
<nr2>
MEAS:SPECT:CURR1:THD?
2.5600
MEASure:SPECTrum:EHD?
Returns Even Harmonic Distortion of the most recent
:MEASure:SPECTrum:parameter command
<nr2>
MEAS:SPECT:EHD?
3.5690
MEASure:SPECTrum:VOLTage#:EHD?
Same as "MEAS:SPECTrum:EHD?" but selects voltage and phase
#.Returns Even Harmonic Distortion of the selected phase voltage.
<nr2>
MEAS:SPECT:VOLT1:EHD?
10.5891
MEASure:SPECTrum:VLL#:EHD?
Same as "MEAS:SPECTrum:EHD?" but selects Line to Line voltage
#.Returns Even Harmonic Distortion of the selected Line to Line
voltage.
<nr2>
MEAS:SPECT:VLL1:EHD?
10.5891
MEASure:SPECTrum:CURRent#:EHD?
Same as "MEAS:SPECTrum:EHD?" but selects current and phase
#.Returns Even Harmonic Distortion of the selected phase currebt.
<nr2>
MEAS:SPECT:CURR1:EHD?
22.5948