Pacific Power Source LMX Series Operation Manual page 276

Programmable ac power source
Table of Contents

Advertisement

Query Syntax
Description
Query Example
Query Syntax
Description
Query Example
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Returned Data Format
Query Example
Query Syntax
Description
Query Example
Query Syntax
Description
Query Example
Query Syntax
Description
Query Example
Query Syntax
Description
Query Example
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
[SOURce:]PROTect[:RMS]:KVA:LEVel:MAXimum?
This command returns the maximum apparent power protection
level setting.
PROT:KVA:LEV:MAX?
41.667
[SOURce:]PROTect[:RMS]:KVA:LEVel:DEFault?
This command returns the default apparent power protection level
setting. This value will be a function of the power source model.
PROT:KVA:LEV:DEF?
41.667
[SOURce:]PROTect[:RMS]:KVA:TDELAY <DELAY>
This command sets the apparent power protection trip delay time.
Setting is in multiples of 100 msec so 5 equals 500 msec.
< LEVEL >
<nr2>
PROT:KVA:LEV 5
[SOURce:]PROTect[:RMS]:KVA:TDELAY?
<b>
PROT:KVA:TDELAY?
5.000
[SOURce:]PROTect[:RMS]:KVA:TDELAY:MINimum?
This command returns the minimum apparent power protection trip
delay time setting.
PROT:KVA: TDELAY:MIN?
0
[SOURce:]PROTect[:RMS]:KVA:TDELAY:MAXimum?
This command returns the maximum apparent power protection trip
delay time setting.
PROT:KVA: TDELAY:MAX?
3000
[SOURce:]PROTect[:RMS]:KVA:TDELAY:DEFault?
This command returns the default apparent power protection trip
delay time setting.
PROT:KVA:TDELAY:DEF?
5
[SOURce:]PROTect[:RMS]:KVA:TRIPped?
This command returns the apparent power protection trip status.
Returns 1 if tripped or 0 if not.
PROT:KVA:TRIP?
41.667
LMX SERIES™ OPERATION MANUAL
Remote Control Programming
SECTION 8:
Page 276 of 463