Access to other utility screens is available from the UNIT CONFIGURATION screen through
the soft keys. The table below lists the available soft keys on the UNIT CONFIGURATION
screen.
SOFT KEY
User Limits (SK1)
Ramp & Slew (SK3)
Program Memory (SK2)
CSC Config. (SK4)
Next Screen (SK5)
UNIT CONFIGURATION 2 OF 2 ----------------------------------------------------------------------------------
Allow Output Enable at Power On
Enable Current Overload
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
of the installed output transformers.
Note: In either coupled mode, only AC voltage
programming is possible.
Description
Displays SETUP MENU screen. Refer to section 0
Displays SLEW RATE MENU screen. Refer to section 6.7.3
Displays PROGRAM MEMORY screen. Refer to section 0
Display CSC setting screen
Toggle to alternate UNIT CONFIGURATION screen

Table 6-20: Available UNIT CONFIGURATION 1 screen soft keys

power up.
Current Overload mode allows the power source to provide
more than the nominal max. RMS current (around 30
percent more) for a short period (up to 2 seconds). When
enabled, the user can set the CURR:LIM 30% higher than
whit this mode off. For example in a stand-alone 360LMX
unit in three phase mode (FORM 3), RMS output current
can be up to 55A when the continuous output limit is 16A.
A warning message will be displayed notifying the user this
mode is being enabled.
LMX SERIES™ OPERATION MANUAL
SECTION 6:
This mode if set, causes the output to turn on at
Front Panel Operation