System Remote Access Commands - Pacific Power Source LMX Series Operation Manual

Programmable ac power source
Table of Contents

Advertisement

8.9.12 System Remote Access Commands

Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Returned Data Format
Query Example
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
SYSTem:REMote:ACCESS
Sets remote access permission.
<0 | DISABLED | 1 | ENABLED>
<b>
SYST:REM:ACCESS 1
SYSTem:REMote:ACCESS?
<cr>
SYST:REM:ACCESS?
1
SYSTem:REMote:ACCESS:REQuest
This commands results in a pop up dialog on the front panel display
requesting the local user to ACCEPT. Confirms presence of a person
at the location of the instrument.
Alias name. (This argument is optional)
<cr>
SYSTem:REMote:ACCESS:REQuest
None
SYSTem:REMote:ACCESS:LOGIN
This command uses a password as an argument to request access to
the instrument. The password can be set on the front panel or using
the SYSTem:REMote:PASSword command
Password
<nr1>
SYSTem:REMote:ACCESS:LOGIN 1234
None