Output Bandwidth; Load Transient Response; Output Dc Offset; Output Protection - Pacific Power Source ASX series Operation Manual

Table of Contents

Advertisement

2.1.8 OUTPUT BANDWIDTH

The output bandwidth of the ASX-Series Power Source is listed below.
Full Power:
Small Signal:
( rated at 10% of full-scale output voltage )

2.1.9 LOAD TRANSIENT RESPONSE

Output load transient response for a 10-90% load induced step transient is approximately
60 μsec.

2.1.10 OUTPUT DC OFFSET

The DC offset present on the output of the ASX-Series Power Source is less than 5 mVDC.

2.1.11 OUTPUT PROTECTION

The output of the ASX-Series Power Source is protected through the use of electronic current
limiting. The output will automatically recover when the output fault is removed. Thermal
overload protection is also provided. Refer to paragraph 2.3.3 for details.
Note:
The programmable controller also provides programmable current limit.
Refer to the UPC-Series Operation Manual for details.

2.1.12 OUTPUT CONTROL CHARACTERISTICS

Output control characteristics, sync I/O signals, and metering capabilities are determined by the
controller which is installed. Refer to the controller manual for details.

2.1.13 OUTPUT ISOLATION

The output of the ASX-Series is galvanically isolated from the chassis and input power. Output
Neutral to Chassis voltage is allowed to be 150 VAC, maximum. (Refer to Paragraph 3.4.4 for
special considerations when using transformer-coupled outputs.)
15
to
400 Hz (±0.10 db [± 1%])
400
to
1,200 Hz (±0.25 db [± 3%])
5
to
2,500 Hz (±0.5 db [±6%])
23