Step 5.
A search for the device begins, and the research result is displayed.
To cancel a defect search, touch [ESC].
During a defect search, all key operations except [ESC] and [Exit] are invalid.
■2. Search result
Search results reveal any occurrences of the search device. They are useful when you determine whether a defective
device is conductive or nonconductive.
If any occurrence of the search device is not found as a result of the search, a message appears on-screen, telling that
"PROGRAM NOT FOUND."
(1) When an occurrence of the search device is found:
If an occurrence of the search device is found as a result of the search, the search for another defective device will
automatically be started.
Example: After searching for Device M120 that is in the OFF state, "M669" will be displayed as a device that caused
a failure.
The next defect is automatically
searched.
POINT
POINT
POINT
Operation before a defect search
In the case of the FX ladder monitor, touch [Mon.] before starting a defect search.
If you touch [Xref.] without touching [Mon.], the message "NO MONITORING" will be displayed.
After searching for Coil M120 that is in the OFF state,
"M669" is displayed as a device that is not conductive.
Example:
* After searching for a device that is in the ON state, a device that is conductive
is displayed. The entire field of the device name and number is highlighted on-
screen.
Example:
After searching for Coil M669 that is in the OFF state,
"M111" is displayed as a device that is not conductive.
Example:
When there is no more defect, the "FACTOR SEARCH STOP" will be displayed,
and the defect search will end.