Mitsubishi Electric GOT2000 Series User Manual page 382

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■2. Creating a controller list file
For the controller list file, set the network No. and the station number of the controller to be backed up or restored.
The controller list file can be set to each backup setting file.
(1) Controller list file specification
(a)
Specification
File name, extension
File format
Encode format
(b)
Format
Up to 64 controllers to be backed up or restored can be set. (The 65th or later are invalid.)
When performing the backup/restoration, the controller list file settings are executed from the top.
No.
1)
Header
2)
Data version
3)
Controller list
4)
Execution/non-execution
5)
Network No.
6)
Station No.
7)
Memo
10 - 40
10.3 Operations for Display
Item
SYSnNET.INI
(Assign the CH No. to be backed up or restored to "n" in the file name.)
Unicode text format
Little endian with UTF-16 BOM
4)
Item
POINT
POINT
POINT
Precautions for creating a controller list file
(1) When " is entered
• Even if " is entered in the memo, it is not treated as a quotation mark for the character
string, the text to the line feed is considered a character string.
• If numerical values are put in "s, a format error occurs.
(2) When creating with a text editor
When the controller list file is created with a text editor, delimit data with tabs.
If unnecessary tabs are entered, a format error occurs.
5)
6)
Indicates that it is the controller list file.
Displays the data version of the controller list file.
Set the version to 1.
Indicates the title of the controller list.
Set whether to execute or not the backup/restoration.
For controllers other than servo amplifiers and inverters
0: Not executed, 1: Executed
For servo amplifiers and inverters
2: Not executed, 3: Executed
Set the network No. of controllers to be backed up or restored. (0 to 239)
Set the station No. of controllers to be backed up or restored. (0 to 120)
If the network No. is 0, 255 (host) can also be set.
Both 2-byte and 1-byte characters can be set.
Up to 30 characters are displayed in the controller list screen.
Setting
7)
Setting
1)
2)
3)

Advertisement