2) [F-loop]
This shows the status of the F-loop (Forward loop).
The following shows the display items.
• [OK]
• [NG]
The loop names vary depending on the network system to be monitored as shown below.
MELSECNET(II) network systems
Forward loop
3) [R-loop]
This shows the status of the R-loop (Reverse loop).
The following shows the display items.
• [OK]
• [NG]
The loop names vary depending on the network system to be monitored as shown below.
MELSECNET(II) network systems
Reverse loop
4) [Loop back]
This shows whether the loopback was executed or not.
The following shows the display items.
• [Executed]
• [Not executed]
5) [Link scan time]
This shows the link scan time required for the control station and the normal station, for the remote master
station and the remote I/O station, and for the master station and all the sub-stations.
The following shows the display items.
[Maximum]
[Minimum]
[Current]
6) Communication status
This shows the communication status of the host.
The status of only a local station in the MELSECNET(II) network is displayed.
The following shows the display items.
[P-MTR WAIT]
[Cyclic com]
[Com. suspension]
7) Network name
This shows the network category, network number, and station number.
6 - 14
6.4 Operation Procedures
MELSECNET/H,
MELSECNET/10,
MELSECNET/H,
MELSECNET/10,
Item
The maximum value of link scan time
The minimum value of link scan time
The current value of link scan time
Item
Ready to receive parameters from the master station
Normal communication
Communication is suspended because the host is disconnected
CC-Link IE controller network
OUT-side loop
CC-Link IE controller network
IN-side loop
CC-Link IE field network
PORT1-side loop
CC-Link IE field network
PORT2-side loop
Description