(9) When another trigger condition is met during backup
The GOT cannot detect that another trigger condition is met.
Trigger device
(Trigger ID: 1)
Trigger device
(Trigger ID: 2)
Backup processing
(Trigger ID: 1)
Backup processing
(Trigger ID: 2)
Process notification
device
(Trigger ID: 1)
Process notification
device
(Trigger ID: 2)
Trigger backup processing
setting No. notification
(GS657)
For ensuring the trigger backup, establish a handshake with the trigger device and the process notification device.
An example of a handshake is shown on the next page.
Trigger device
(Trigger ID: 1)
Trigger device
(Trigger ID: 2)
Backup processing
(Trigger ID: 1)
Backup processing
(Trigger ID: 2)
Process notification
device
(Trigger ID: 1)
Process notification
device
(Trigger ID: 2)
Trigger backup processing
setting No. notification
(GS657)
Step 1.
The trigger device (Trigger ID: 1) turns on, and then the GOT starts the backup (Trigger ID: 1).
Step 2.
When the backup is started, the process notification device (Trigger ID: 1) turns on, and the trigger
backup processing setting No. notification (GS657) stores the trigger ID.
When the process notification device turns on, the trigger device (Trigger ID: 1) turns off.
Step 3.
When the backup (Trigger ID: 1) is completed, the GOT recognizes that the trigger device (Trigger ID: 2)
is on and the GOT starts the backup (Trigger ID: 2).
Step 4.
When the backup is started, the process notification device (Trigger ID: 2) turns on, and the trigger
backup processing setting No. notification (GS657) stores the trigger ID.
When the process notification device turns on, the trigger device (Trigger ID: 2) turns off.
not
detected
1
0
1
2
10.3 Operations for Display