Mitsubishi GOT1000 Series Connection Manual page 83

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

3
Setting Stage No. and Slot No.
Before setting Stage No. and Slot No.
The PLC CPU recognizes the GOT as follows.
At the [Communication Detail Settings], assign the GOT to an empty I/O slot on the
PLC CPU.
(1) When connecting to QCPU (Q mode)
Set an additional stage (16 points x 10 slots) for GOT connection, and assign a GOT to one of the
I/O slots.
(The GOT cannot be assigned to empty slots of the main base unit or extension base unit.)
Main base unit
Q312B
Extension base unit
Q68B
When using the bus extension connector box
Set the Stage No. switch on the bus extension connector box to the same Stage No.
as the GOT.
For setting details, refer to the following manual:
• QCPU (Q mode)
• Other than QCPU (Q mode) : Intelligent function module of 32 I/O points
Stage No.
:2
Stage No.
:2
Slot No.
:0
Slot No.
:1
A9GT-QCNB Bus Extension Connector Box User's Manual
2.2 Preparatory Procedures for Monitoring
2.2.3 Setting communication interface (Communication settings)
: Intelligent function module of 16 I/O points
Extension
stage 1
Stage No. setting
connector
Stage No.
:2
Slot No.
:2
1
2
3
4
5
6
7
8
2 - 31