When designing the system
When the GOT is OFF, the following currents are supplied to the GOT from the PLC CPU side (the
power supply module on the main base unit). (The GOT does not operate when it is OFF.)
Design the system so that the 5V DC current consumption of the modules on the main base unit and the
total current consumption of the GOTs will not exceed the rated output current of 5V DC of the power
supply module in use.
When connecting to
QCPU (Q mode)
Other than QCPU (Q mode)
8
When assigning GOT I/O signals
Do not use the I/O signals assigned to the PLC CPU in sequence programs, as these signals are used
by the GOT system.
When these signals are used, GOT functions cannot be assured.
9
When connecting to a QCPU (Q mode)
(1) Restrictions in overall cable length to No. of GOTs
The following restrictions apply when 3 of more GOTs are connected:
Number of GOTs
1
2
3
4
5
(2) When using a Q00JCPU
The bus extension connector box can be connected only to the extension base unit.
(Connecting it to the main base unit is not allowed.)
2 - 46

2.3 Precautions

Overall Cable Length
Less than 25m
Less than 20m
Less than 15m
Q00JCPU
No. of GOTs
5
4
3
2
1
3
2
1
Restriction
Overall Cable Length
(No restrictions)
(No restrictions)
Total current consumption
2200mA
1760mA
1320mA
880mA
440mA
360mA
240mA
120mA
Restriction
25 to 37m
Use the same power
supply for the PLC and
20 to 37m
all GOTs, and turn these
devices ON and OFF
15 to 37m
simultaneously.