Using The Controller Link Support Software (Ver. 2.00 Or Later) And Cx-Programmer; Using Fins Commands - Omron SYSMAC CS1W-CLK13 Operation Manual

Optical ring controller link units, h-pcf/gi cable
Table of Contents

Advertisement

Starting and Stopping Data Links
5-3-2
Using the Controller Link Support Software (Ver. 2.00 or Later)
and CX-Programmer
Using a Programming Device Connected to PLC Node
Using a Computer Node
5-3-3

Using FINS Commands

Issuing the FINS Command from a Computer Node
Issuing the FINS Command from CVM1, CV-series, and CS-series
startup node for data links (Data Link Start/Stop Bit in the CS1D System CPU
Unit is OFF), and the relevant node is operating as a polling node, the net-
work's data links may stop if an ACT/STB (active/standby) switchover error
occurs.
Data links can be started or stopped using commands on the Data Link Menu
of the Controller Link Support Software (Ver. 2.00). The node for which start-
ing and stopping is being specified must participate in the data links.
IBM PC/AT or
Controller Link Support Software (Ver. 2.00 or later)
or CX-Net (in CX-Programmer)
compatible
Note Use the CX-Net (in CX-Programmer).
IBM PC/AT or
compatible
Controller Link
Support Board
Data links can be started or stopped from the Controller Link Support Board
on the local node.
Data links can be started and stopped by sending the RUN and STOP FINS
commands from a node on the Controller Link to a node that is in the data
links.
IBM PC/AT or
compatible
Controller Link
Support Board
CVM1, CV or CS
FINS command:
RUN/STOP
Data links can be stopped by sending the FINS command "STOP." The node
to which the FINS command is issued must be participating in the data link.
Start/stop data links
Controller Link Support
Software (Ver. 2.00 or later)
Start/stop data links
FINS command:
RUN/STOP
Node in data links
Section 5-3
Node in data links
Node in data links
Node in data links
129