Channel 0
- temp
2 mA
X521.1
-
X521.2
+
KTY/PTC/
+ temp
Bimetal/PT1000
Channel 1
- temp
2 mA
X521.3
-
X521.4
+
KTY/PTC/
+ temp
Bimetal/PT1000
<1> p4100[0...3]
= 0: Evaluation disabled
= 1: PTC
= 2: KTY
= 4: Bimetal break contact
= 6: PT1000
<2> An alarm A35920 or A35921 in the temperature evaluation channel 0 or 1 of
the TM120 is signaled to the next (downstream) drive control via the special
temperature actual value -300 °C.
<3> As a result of the wire breakage monitoring the maximum temperature that
can be measured is limited to approximate 188.6 °C.
<4> A value > 250 °C de-activates the alarm or fault.
1
2
DO: TM120
Terminal Module 120 (TM120) - Temperature evaluation channels 0 and 1
PT1000
Sensor type
p4100[0]
<1>
T = 64 ms
A
KTY
Resistance
calculation
D
PTC
Bimetal
Temperature sensor channel 0
r4101[0]
PT1000
Sensor type
p4100[1]
<1>
T = 64 ms
A
KTY
Resistance
calculation
D
PTC
Bimetal
Temperature sensor channel 1
r4101[1]
<5> For KTY/PT1000: p4103[0...3] = 0 Output from Timer always off (0).
For PTC/bimetal: p4103[0...3] = 0 delay time = 0 s.
<6> KTY/PT1000 = For monitoring wire breakage and short-circuit.
PTC = For monitoring short-circuit.
Bimetal = No monitoring.
3
4
<3>
188.6 °C
R
Sensortype
T
p4100
<1>
-99 °C
6
<3>
188.6 °C
Bimetal
4
R
KTY
2
PTC
1
T
0
-300 °C
-140 °C
1
0
1
0
250 °C
-50 °C
PTC: 1650 Ohm
Measured temperature
Bimetal: 100 Ohm
<3>
188.6 °C
R
Sensortype
T
p4100
<1>
-99 °C
6
<3>
188.6 °C
Bimetal
4
R
KTY
2
PTC
1
T
0
-300 °C
-140 °C
1
0
1
0
250 °C
-50 °C
PTC: 1650 Ohm
Bimetal: 100 Ohm
Measured temperature
5
fp_9605_51_eng.vsd
11.02.16 V04.08.00
Channel 0 alarm threshold
-48...251 [°C]
p4102[0] (251)
<4>
p4103[0]
1
<5>
T
0
0
Channel 0 fault threshold
1
-48...251 [°C]
p4102[1] (251)
1
<6>
0
A35920
"Error temperature sensor channel 0"
5 K
<2>
<6>
Alarm is not present
0
Alarm is present
-300 °C
1
Channel 1 alarm threshold
-48...251 [°C]
p4102[2] (251)
<4>
p4103[1]
1
<5>
T
0
0
Channel 1 fault threshold
1
-48...251 [°C]
p4102[3] (251)
1
<6>
0
A35921
"Error temperature sensor channel 1"
5 K
<2>
<6>
Alarm is not present
0
Alarm is present
-300 °C
1
6
7
Function diagram
SINAMICS
4000.00 μs
r4104.0
A35211
"Temperature
alarm threshold
channel 0
exceeded"
r4104.1
F35207
"Temperature
fault/alarm
threshold channel 0
exceeded"
Temperature actual
value channel 0
r4105[0]
r4104.2
A35212
"Temperature
alarm threshold
channel 1
exceeded"
r4104.3
F35208
"Temperature
fault/alarm
threshold channel 1
exceeded"
Temperature actual
value channel 1
r4105[1]
8
- 9605 -