02 Digital Input/Output Parameter
Two-wire / Three-wire Operation Control
Settings
 This parameter sets the configuration of the terminals (Pr.00-21=1 or Pr.00-31=1) which control
the operation. There are three different control modes listed in the following table.
Pr.02-00
Settings: 0
2-wire mode 1
FWD/STOP
REV/STOP
Settings: 1
2-wire mode 2
RUN/STOP
REV/FWD
Settings: 2
3-wire operation control
Multi-function Input Command 1 (MI1)
Multi-function Input Command 2 (MI2)
Multi-function Input Command 3 (MI3)
Multi-function Input Command 4 (MI4)
Multi-function Input Command 5 (MI5)
Multi-function Input Command 6 (MI6)
Multi-function Input Command 7 (MI7)
Multi-function Input Command 8 (MI8)
Input terminal of I/O extension card (MI10)
Input terminal of I/O extension card (MI11)
Input terminal of I/O extension card (MI12)
0: Two-wire mode 1, power on for operation control
1: Two -wire mode 2, power on for operation control
2: Three-wire, power on for operation control
12.1-02-1
Chapter 12 Description of Parameter SettingsC2000
 This parameter can be set during operation.
Control Circuits of the External Terminal
Default: 0
Default: 1
Default: 2
Default: 3
Default: 4