Chapter 2 InstallationC2000
2-1 Mounting Clearance
Prevent fiber particles, scraps of paper, shredded wood saw dust, metal particles, etc. from
adhering to the heat sink
Install the AC motor drive in a metal cabinet. When installing one drive below another one,
use a metal separation between the AC motor drives to prevent mutual heating and to
prevent the risk of fire accident.
Install the AC motor drive in Pollution Degree 2 environments only:
Normally only nonconductive pollution occurs and temporary conductivity caused by
condensation is expected.
The appearances shown in the following figures are for reference only.
Airflow direction:
Single drive installation
(Frame A–H)
Multiple drives, single
side-by-side horizontal
installation(Frame G, H)
Multiple drives, side-by-side
installation (Frame D0, D, E,
F) Install metal separation
between the drives.
Multiple drives side-by-side vertical installation (Frame A–H )
Ta: Frame A–G
When installing one AC motor drive below another one (top-bottom installation), use a metal separation
between the drives to prevent mutual heating. The temperature measured at the fan's inflow side must
be lower than the temperature measured at the operation side. If the fan's inflow temperature is higher,
use a thicker or larger size of metal seperation. Operation temperature is the temperature measured at
50mm away from the fan's inflow side. (As shown in the figure below)
(Blue arrow) inflow
Ta*: Frame H
(Red arrow) outflow
Side-by-side horizontal installation(Frame A–C)
2-2
Distance