Serial Connection
Parallel Connection
Feedback Signal Detection Time
Settings
 Pr. 08-08 is valid only for ACI 4–20mA.
 This parameter sets the detection time for abnormal PID signal feedback. Setting the detection
time to 0.0 disables the detection function.
Feedback Signal Fault Treatment
Settings
 This parameter is valid only for ACI 4–20mA.
 AC motor drive acts when the analog PID feedback is abnormal.
Sleep Reference
Settings
 Determines the sleep frequency, and if the sleep time and the wake-up frequency are enabled
or disabled. Pr. 08-10 = 0: Disabled; Pr. 08-10 ≠ 0: Enabled.
0.0–3600.0 sec.
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
0.00–599.00 Hz
12.1-08-7
Chapter 12 Description of Parameter SettingsC2000
Default: 0.0
Default: 0
Default: 0.00