Chapter 11 Summary of Parameter SettingsC2000

06 Protection Parameters

Pr.
Parameter Name
06-00
Low voltage level
06-01
Over-voltage stall prevention
Selection for over-voltage stall
 06-02
prevention
Over-current stall prevention
06-03
during acceleration
Over-current stall prevention
06-04
during operation
Setting Range
230V:
Frame A–D: 150.0–220.0V
Frame E and above: 190.0–220.0V
460V:
Frame A–D: 300.0–440.0V
Frame E and above: 380.0~440.0V
575V: 420.0–520.0V
DC
690V: 450.0–660.0V
DC
0: Disabled
230V: 0.0–450.0V
DC
460V: 0.0–900.0V
DC
575V: 0.0–920.0V
DC
690V: 0.0–1087.0V
DC
0: Traditional over-voltage stall prevention
1: Smart over-voltage stall prevention
230V / 460V models
Normal load: 0–160% (100% corresponds to the rated
current of the drive)
Heavy load: 0–180% (100% corresponds to the rated
current of the drive)
575V / 690V models
Light load: 0–125% (100% corresponds to the rated
current of the drive)
Normal load: 0–150% (100% corresponds to the rated
current of the drive)
Heavy load: 0–180% (100% corresponds to the rated
current of the drive)
230V / 460V models
Normal load: 0–160% (100% corresponds to the rated
current of the drive)
Heavy load: 0–180% (100% corresponds to the rated
current of the drive)
575V / 690V models
Light load: 0–125% (100% corresponds to the rated
current of the drive)
Normal load: 0–150% (100% corresponds to the rated
current of the drive)
Heavy load: 0–180% (100% corresponds to the rated
current of the drive)
11-30
DC
DC
DC
DC
Default
180.0
200.0
360.0
400.0
470.0
480.0
380.0
760.0
920.0
1087.0
0
120
120
120
120
150
120
120
120
120
150