Delta C2000 Series User Manual page 518

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

T (°C)
200
100
0
1.50
-100
 When the temperature exceeds the setting level, an oH3 error occurs to the drive. Reset
conditions: when the temperature is below the trigger level -5ºC, the oH3 error is cleared.
 When the KTY is not connected, or the KTY is burned, the calculated temperature is beyond
-40–150ºC, the temperature is displayed as its lower limit (-40ºC) or upper limit (150ºC) without
additional error information. At this time, the drive still trips up the oH3 error, check if the
installation is correct.
 When the temperature detection warning occurs to the KTY-84, select the action according to Pr.
06-29.
C2000 / KTY84-130 Temperature and voltage diagram
2.00
2.50
12.1-06-26
Chapter 12 Description of Parameter SettingsC2000
y = 79.717x - 156.64
3.00
3.50
C2000
Linear (C2000)
4.00
Analog voltage (V)