Delta C2000 Series User Manual page 39

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Chapter 2 InstallationC2000
NOT E
The mounting clearances stated in the figure is for installing the
drive in an open area. To install the drive in a confined space (such
as cabinet or electric box), please follow the following three rules:
(1) Keep the minimum mounting clearances. (2) Install a ventilation
equipment or an air conditioner to keep surrounding temperature
lower than operation temperature. (3) Refer to parameter setting
and set up Pr. 00-16, Pr.00-17, and Pr. 06-55.
The following table shows the heat dissipation and the required air
volume when installing a single drive in a confined space. When
installing multiple drives, the required air volume shall be multiplied
by the number of the drives.
Refer to the chart (Air flow rate for cooling) for ventilation
equipment design and selection.
Refer to the chart (Power dissipation) for air conditioner design and
selection.
Different control mode will affect the derating. See Pr. 06-55 for
more information.
Ambient temperature derating curve shows the derating status in
different temperature in relation to different protection level.
If UL Type 1 models need side by side installation, please remove
top cover of FrameA–C, and please do not install conduit box of
Frame D and above.
Suitable for Installation in a Compartment Handling Conditioned Air
(Plenum).
2-4