Chapter 12 Description of Parameter SettingsC2000
Acceleration / Deceleration Time Selection of Stall Prevention at Constant Speed
Settings
 Sets the acceleration / deceleration time selection when stall prevention occurs at constant
speed.
Over-torque Detection Selection (OT1)
Settings
Over-torque Detection Selection (OT2)
Settings
 When you set Pr. 06-06 and Pr. 06-09 to 1 or 3, a warning message displays, but there is no error
record.
 When you set Pr. 06-06 and Pr. 06-09 to 2 or 4, a warning message displays and there is an error
record.
0: By current acceleration / deceleration time
1: By the 1
acceleration / deceleration time
st
2: By the 2
acceleration / deceleration time
nd
3: By the 3
acceleration / deceleration time
rd
4: By the 4
acceleration / deceleration time
th
5: By automatic acceleration / deceleration
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
12.1-06-5
Default: 0
Default: 0
Default: 0