01 Basic Parameters

Maximum Operation Frequency
Settings
 Determines the AC motor drive's maximum operation frequency range. This setting corresponds
to the maximum value for the analog input frequency setting signal (0 – +10 V, 4–20 mA,
0–20 mA, ±10 V).
 In normal load mode:
VF, SVC, VFPG, FOCPG: 0–599 Hz
FOC sensorless (IM/PM): 0–300H z/ 500 Hz
 In heave load mode:
Output range: 0–300 Hz
Output Frequency of Motor 1(base frequency and motor rated frequency)
Output Frequency of Motor 2(base frequency and motor rated frequency)
Settings
 Set the value according to the motor's rated frequency from the motor's nameplate. If the motor's
rated frequency is 60 Hz, set the value to 60 Hz. If the motor's rated frequency is 50 Hz, set the
value to 50 Hz.
Output Voltage of Motor 1(base frequency and motor rated frequency)
Output Voltage of Motor 2(base frequency and motor rated frequency)
Settings
 Set the value according to the motor's rated voltage from the motor's nameplate. If the motor's
rated voltage is 220 V, set the value to 220.0 V. If the motor's rated voltage is 200 V, set the value
to 200.0 V.
 There are a wide variety of motors, but the power system for each country is different. The
convenient and economical way to solve this problem is to use an AC motor drive, which can deal
with different voltages and frequencies, while supporting the original characteristics and life of the
motor.
Mid-point Frequency 1 of Motor 1
Settings
00.00–599.00 Hz
0.00–599.00 Hz
230V series: 0.0–255.0 V
460V series: 0.0–510.0 V
575V series: 0.0–637.0 V
690V series: 0.0–765.0 V
0.00–599.00 Hz
12.1-01-1
Chapter 12 Description of Parameter SettingsC2000
 You can be set this parameter during operation.
Default: 60.00 / 50.00
Default: 60.00 / 50.00
Default:
200.0 / 400.0 / 575.0 / 660.0
Default: 3.00