Chapter 12 Description of Parameter SettingsC2000
 When Pr. 02-57 = 0, the output current is lower than the setting of Pr. 02-33 Pivot Point of the
current (< Pr. 02-33) or when output frequency is lower than the setting of Pr. 02-58(< Pr. 02-58),
disable the setting of #42 of the multi-function output Pr. 02-13, Pr. 02-14, Pr. 02-16 and Pr.
02-17.
 For crane application, when MOx=42, the setting of Pr. 02-34 must be greater than Pr. 02-58;
and Pr. 02-33 must be greater than Pr. 02-57.
Frequency Reached Detection Amplitude
Settings
IO Card Type
Settings
DFM Output Selection
Settings
Internal/External Multi-function Input Terminals Selection
Settings
 This parameter is used to select the terminals MI1~MI15 to be internal terminal or external
terminal. When the MIx has set as internal terminal, then the corresponding external terminal
function will be disabled.
 To activate internal terminals via Pr. 02-75 setting.
 The setting method is to convert binary number to hexadecimal number for input.
0.00~599.00Hz
Read only
1: EMC-BPS01 Card
4: EMC-D611A Card
5: EMC-D42A Card
6: EMC-R6AA Card
11: EMC-A22A
0: Use frequency with speed control as DFM output frequency
1: Use frequency with system accel./decel. as DFM output frequency
0000~FFFFh
12.1-02-28
Default: 0.00
Default: Read only
Default: 0
Default: 0000h