Accumulated Watt-hour for a Motor (W-hour)
Settings
Accumulated Watt-hour for a Motor in Low Word (kW-hour)
Settings
Accumulated Watt-hour for a Motor in High Word (MW-hour)
Settings
 Pr.05-28–05-30 records the amount of power consumed by the motors. The accumulation begins
when the drive is activated and the record is saved when the drive stops or turns OFF. The
amount of consumed watts continues to accumulate when the drive is activated again. To clear
the accumulation, set Pr. 00-02 as 5 to return the accumulation record to 0.
 The accumulated total watts of the motor per hour = Pr. 05-30 x 1000000 + Pr. 05-29 x 1000 + Pr.
05-28 Wh
Example: When Pr. 05-30 = 76 MWh and Pr. 05-29 = 150 kWh, Pr. 05-28 = 400 Wh (or 0.4kWh),
the accumulated total kilowatts of the motor per hour = 76 x 1000000 + 150 x 1000 + 40 =
76150400Wh = 76150.4kWh
Read only
Read only
Read only