Chapter 12 Description of Parameter SettingsC2000
when KPC-CC01 is installed with firmware version higher than version 1.021). Set the LOCAL
frequency and operation source with Pr.00-20 and Pr.00-21. Set the REMOTE frequency and
operation source with Pr.00-30 and Pr.00-31. Select or switch LOC / REM mode with the digital
keypad KPC-CC01 (optional) or set the multi-function input terminal MI = 56. The AUTO key of
the digital keypad is for the REMOTE function, and HAND key is for the LOCAL function.
 When you set the external terminal (MI) to 56 for LOC / REM mode selection, if you set Pr.00-29
to 0, then the external terminal function is disabled.
 When you set the external terminal (MI) to 56 for LOC / REM mode selection, if Pr.00-29 is not
set to 0, then AUTO / HAND key is disabled, and the external terminal has the highest command
priority. 
Master Frequency Command (HAND) Source
Settings
 Determines the master frequency source in HAND mode.
Operation Command (HAND) Source
Settings
 Set the source of the master frequency in HAND mode.
 Pr. 00-20 and Pr. 00-21 are for the settings of frequency source and operation source in AUTO
mode. Pr. 00-30 and Pr. 00-31 are for the settings of frequency source and operation source in
HAND mode. You can switch the AUTO / HAND mode with the keypad KPC-CC01 (optional) or
the multi-function input terminal (MI) to set the master frequency source.
 The default for the frequency source or operation source is for AUTO mode. It returns to AUTO
mode whenever cycle the power. If you use a multi-function input terminal to switch between
AUTO and HAND mode, the highest priority is the multi-function input terminal. When the
external terminal is OFF, the drive does not accept any operation signal and cannot execute JOG.
0: Digital keypad
1: RS-485 communication
2: External analog input (Pr. 03-00)
3: External UP/DOWN terminal (multi-function input terminal)
4: Pulse input without direction command (Pr. 10-16 without direction)
5: Pulse input with direction command (Pr. 10-16)
6: CANopen communication card
8: Communication card (does not include CANopen card)
0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 communication. Keypad STOP disabled.
3: CANopen communication card
5: Communication card (does not include CANopen card)
12.1-00-18
Default: 0
Default: 0