Chapter 2 InstallationC2000
Model No.
External Internal
VFD370C63B-21
VFD450C63B-00/21
175.9
VFD550C63B-00/21
175.9
VFD750C63B-00/21
264.6
VFD900C63B-00/21
264.6
VFD1100C63B-00/21 264.6
VFD1320C63B-00/21 264.6
VFD1600C63B-00/21 248.1
VFD2000C63B-00/21 248.1
VFD2500C63B-00/21
VFD3150C63B-00/21
VFD4000C63B-00/21
VFD4500C63B-00/21
VFD5600C63B-00/21
VFD6300C63B-00
VFD6300C63B-21
The required airflow shown in chart is for installing single drive in a
confined space.
When installing the multiple drives, the required air volume should be the
required air volume for single drive X the number of the drives.
Air flow rate for cooling
Flow Rate [cfm]
Total
89.0
21.3
110.3
36.4
212.3
36.4
212.3
90.6
355.2
90.6
355.2
90.6
355.2
90.6
355.2
135.3
383.4
135.3
383.4
409.7
409.7
563.0
952.9
952.9
952.9
Flow Rate [m
/hr]
3
External Internal
Total
151.2
36.2
187.5
298.8
61.8
360.6
298.8
61.8
360.6
449.6
153.9
603.5
449.6
153.9
603.5
449.6
153.9
603.5
449.6
153.9
603.5
421.6
229.9
651.4
421.6
229.9
651.4
696.0
696.0
956.4
1618.9
1618.9
1618.9
2-6
Power dissipation of AC motor drive
Power Dissipation [W]
Loss External
Internal
(Heat sink)
641.6
283.4
718.2
406.8
890.1
484.9
1356.0
519.0
1652.8
597.2
1960.3
789.7
2230.8
1069.2
2627.3
1372.7
3415.0
1585.0
4751.7
1498.3
5695.4
2179.6
6796.2
3203.8
7313.6
3936.4
9553.4
4446.6
11042.4
4707.6
The heat dissipation shown in
the chart is for installing single
drive in a confined space.
When installing the multiple
drives, volume of heat
dissipation should be the heat
dissipated for single drive X the
number of the drives.
Heat dissipation for each model
is calculated by rated voltage,
current and default carrier.
Total
925.0
1125.0
1375.0
1875.0
2250.0
2750.0
3300.0
4000.0
5000.0
6250.0
7875.0
10000.0
11250.0
14000.0
15750.0