Chapter 12 Description of Parameter SettingsC2000
 Pr. 00-13=2, IM TQC Sensorless control diagram is as follows:
Load Selection
Settings
 Normal load: over-load ability is 160% rated output current in 3 seconds (120% rated output
current in 1 minute). Refer to Pr. 00-17 for the setting of carrier wave. Refer to Chapter 9
"Specifications" or Pr. 00-01 for the rated current.
Heavy load: over-load ability is 180% rated output current in 3 seconds. (150% rated output
current in 1 minute). Refer to Pr. 00-17 for the setting of carrier wave. Refer to Chapter 9
"Specifications" or Pr. 00-01 for the rated current.
 Pr.00-01 varies with the setting value for Pr.00-16. The default value and maximum for Pr.06-03
and Pr.06-04 also vary with the setting value of Pr.00-16.
 In Normal load, the default setting of Pr. 06-03, Pr. 06-04 is 120%, and the maximum is 160%.
However, if DC voltage is higher than 700 V
maximum is 145%
 In Heavy load, the default setting of Pr. 06-03, Pr. 06-04 is 150%, and the maximum is 180%.
However, if DC voltage is higher than 700 V
maximum is 165%
Carrier Frequency
Settings 2–15kHz
 This parameter determines the PWM carrier frequency for the AC motor drive.
Power/ Control
mode
1–15HP
[0.75–11kW]
20–50HP
[15–37kW]
60–125HP
[45–90kW]
0: Normal load
1: Heavy load
230V Series [Normal Load]
VF, VFPG, SVC,
IMFOCPG, IMTQCPG
Settings
Default
2–15kHz
8kHz
4–15kHz
2–10kHz
6kHz
4–10kHz
2–9kHz
4kHz
12.1-00-12
(460V series) or 350 V
DC
(460V series) or 350 V
DC
PMFOCPG,
PMFOC, IPMFOC
PMTQCPG
Settings
Default
Settings
8kHz
4–10kHz
6kHz
4–10kHz
4–9kHz
4kHz
4–9kHz
Default: 0
(230V series), then the
DC
(230V series), then the
DC
Default: Table below
IMFOC, IMTQC
Default
Settings
Default
8kHz
4–14kHz
8kHz
6kHz
4–10kHz
6kHz
4kHz
4–9kHz
4kHz