Chapter 13 Warning CodesC2000
ID No.
Display on LCM Keypad
74
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
The drive detects that DeviceNet
has no power
ID No.
Display on LCM Keypad
75
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
Factory default setting error
ID No.
Display on LCM Keypad
76
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
Noise interference
The memory is broken
Warning Name
ExCom no power
There is no power supply on the DeviceNet
(ECnP)
Action and Reset
There is no power supply on the DeviceNet
Immediately acts
N/A
Re-power
N/A
N/A
Check if the cable and power is normal. If yes, return to the factory for repair.
Warning Name
ExCom factory defect
Factory default setting error
(ECFF)
Action and Reset
Factory default setting error
Immediately acts
N/A
Cycle the power
N/A
N/A
Use DCISoft to reset to the default value.
Warning Name
ExCom inner error
Serious internal error
(ECiF)
Action and Reset
Internal memory saving error
Immediately acts
N/A
Cycle the power
N/A
N/A
Verify wiring of the control circuit, and wiring/grounding of the main circuit to
prevent interference.
Cycle the power.
Reset to the default value and check if the error still exists. If yes, replace the
communication card.
13-34
Description
Corrective Actions
Description
Corrective Actions
Description
Corrective Actions