Delta C2000 Series User Manual page 630

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

ID No.
Display on LCM Keypad
5
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
The upper unit does not transmit
the communication command
within Pr. 09-03 setting time
Malfunction caused by interference
Different communication setting
from the upper unit
Disconnection or bad connection
of the cable
ID No.
Display on LCM Keypad
7
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
Communication connection error
Keypad error
Control board error
Warning Name
Communication error
RS-485 Modbus transmission time-out
10 (CE10)
Action and Reset
When the communication time exceeds the detection time of Pr. 09-03
communication time-out
Setting for Pr. 09-03
N/A
"Warning" occurs when Pr. 09-02=0 and the motor drive keeps running. The
drive resets automatically when receiving the next communication packet.
Immediately reset
N/A
Check if the upper unit transmits the communication command within the setting
time for Pr. 09-03.
Verify the wiring and grounding of the communication circuit. It is recommended
to separate the communication circuit from the main circuit, or wire in 90 degree
for effective anti-interference performance.
Check if the setting for Pr.09-02 is the same as the setting for the upper unit.
Check the cable and replace it if necessary.
Warning Name
Save error 1
Keypad COPY error 1: Keypad copy time-out
(SE1)
Action and Reset
"SE1" warning occurs when the keypad does not transmit the COPY command
to the drive, and does not transmit any data to the drive again in 10 ms at the
time you copy the parameters to the drive.
10 ms
N/A
Manual reset
Immediately reset
N/A
SE1: The causes of error are mostly communication problems between the
keypad and control board. Potential causes include communication signal
interference and the unacceptable communication command to the Slave.
Check if the error occurs randomly, or only occurs when copying certain
parameters (the error displays on the upper right corner of the copy page). If you
cannot clear the error, please contact Delta.
13-3
Chapter 13 Warning CodesC2000
Description
Corrective Actions
Description
Corrective Actions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents