Chapter 12 Description of Parameter SettingsC2000
Automatic Energy-saving Selection
Settings
When energy-saving is enabled, the motor acceleration operates with full voltage. During
constant speed operation, it automatically calculates the best voltage value according to the load
power. This function is not suitable for fluctuating loads or loads which are nearly full during
operation.
When the output frequency is constant (that is, constant operation), the output voltage decreases
automatically as the load decreases. Therefore, the drive operates with minimum multiplication of
voltage and current (electric power).
FOCPG IM:
Steady-speed: Torque current is lower than rated current for 0.35 times and entry into energy
saving mode after 5 seconds.
Return: Torque current is higher than 0.5 times of rated current.
0: Disable
1: Enable
12.1-07-11
Default: 0