Delta C2000 Series User Manual page 684

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

ID*
Display on LCM Keypad
17
Action level
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Check if the ambient temperature
or temperature inside the control
cabinet is too high, or if there is
obstruction in the ventilation hole
of the control cabinet.
Check if there is any obstruction on
the heat sink or if the fan is
running.
Insufficient ventilation space
Check if the drive matches the
corresponding load
The drive has run 100% or more
than 100% of the rated output for a
long time
Unstable power
Load changes frequently
oH1/ oH2 warning level
Model
VFD007C23A
VFD015C23A
VFD022C23A
VFD037C23A
VFD055C23A
VFD075C23A
VFD110C23A
VFD150C23A
VFD185C23A
VFD220C23A
VFD300C23A/E
VFD370C23A/E
VFD450C23A/E
VFD550C23A/E
VFD750C23A/E
VFD900C23A/E
VFD007C43A/E
VFD015C43A/E
VFD022C43A/E
VFD037C43A/E
VFD040C43A/E
VFD055C43A/E
VFD075C43A/E
VFD110C43A/E
Fault Name
Heatsink overheating
(oH2)
Action and Reset
Refer to the table below for oH2 level of each models
When capacitance temperature exceeds the protection level for more than
100ms, oH2 error occurs
N/A
Manual reset
Reset when c
apacitance temperature is lower than oH2 error level minus (-) 10°C
Yes
1. Check ambient temperature.
2. Regularly inspect the ventilation hole of the control cabinet.
3. Change the installed place if there are heating objects, such as braking
resistors, in the surroundings.
4. Install/ add cooling fan or air conditioner to lower the temperature inside the
cabinet.
Remove the obstruction or replace the cooling fan.
Increase ventilation space of the drive.
1. Reduce the load
2. Reduce the carrier
3. Replace the drive with a larger capacity model.
Replace the drive with a larger capacity model.
Install reactor(s)
Reduce load changes
oH1
oH2
95
100
80
110
75
65
95
100
105
110
100
80
14-13
Chapter 14 Fault Codes and DescriptionsC2000
Fault Descriptions
Capacitance temperature exceeds the protection level
Corrective Actions
oH warning
oH1 warning = (Pr.06-15)
oH1 Warning = oH1 – 5
oH2 Warning = oH2 – 5
oH1 Warning = oH1 – 5
oH2 Warning = oH2 – 5