Delta C2000 Series User Manual page 682

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

ID*
Display on LCM Keypad
14
Action level
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Power-off
Incorrect drive models
Power voltage changes
Start up the motor with large
capacity
DC BUS
ID*
Display on LCM Keypad
15
Action level
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Phase loss of input power
Single phase power input to
three-phase model
Power voltage changes
Loose wiring terminal of input
power
The input cable of three-phase
power is cut off
Input power voltage changes too
much
Unbalanced three-phase of input
power
Fault Name
1. DC BUS voltage is lower than Pr. 06-00 setting
Low-voltage at stop
(LvS)
2. Hardware failure in voltage detection
Action and Reset
Pr. 06-00 (Default = depending on the model)
Immediately act when DCBUS voltage is lower than Pr. 06-00
N/A
Manual/ auto
230V series:
Frame A
D = Lv level + 30V
Frame E and above = Lv level + 40V
460V series:
Frame A
D = Lv level + 60V
Frame E and above = Lv level + 80V
575V series:
Frame A
D = Pr. 06-00 + 100.0V
Frame E and above = Pr. 06-00 + 120.0V
690V series:
Frame A
D = Pr. 06-00 + 100.0V
Frame E and above = Pr. 06-00 + 100.0V
500ms
Yes
Improve power supply condition.
Check if the power specification matches the drive.
Adjust voltage to the power range of the drive.
Cycle the power after checking the power. If LvS error still exists, return to the
factory for repair.
Check the power system.
Increase the capacity of power equipment.
Install DC reactor(s).
Fault Name
Phase loss protection
Phase loss of power input
(OrP)
Action and Reset
DC BUS is lower than Pr. 07-00, and DC BUS ripple is higher than Pr. 06-52
N/A
Pr. 06-53
Manual reset
Immediately reset when DCBUS is higher than Pr. 07-00
Yes
Correctly install the wiring of the main circuit power.
Choose the model whose power matches the voltage.
If the main circuit power works normally, verify the main circuit.
Cycle the power after checking the power, if OrP error still exists, return to the
factory for repair.
Tighten the terminal screws according to the torque described in the user
manual.
Wire correctly.
Replace the cut off cable.
Verify the setting value for Pr. 06-50 Time for Input Phase Loss Detection and
Pr. 06-52 Ripple of Input Phase Loss
Check the power three-phase status.
14-11
Chapter 14 Fault Codes and DescriptionsC2000
Fault Descriptions
value at stop
+ 500ms
DC
+ 500ms
DC
+ 500ms
DC
+ 500ms
DC
DC
DC
DC
DC
Corrective Actions
Fault Descriptions
Corrective Actions