Delta C2000 Series User Manual page 408

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Maximum User-Defined Value
Settings
 When Pr. 00-26 is NOT set to 0, the user-defined value is enabled. After selecting the displayed
unit and number of decimal points with Pr.00-25, the setting value of Pr.00-26 corresponds to
Pr.01-00 (Maximum motor operating frequency), and then the motor operation frequency has a
linear relationship with the displayed value on the digital keypad.
Example:
When the frequency set in Pr. 01-00 = 60.00Hz, the maximum user-defined value for Pr. 00-26
is 100.0%. This also means Pr. 00-25 is set at 0021h to select % as the unit.
NOTE
The drive display is controlled by the Pr. 00-25 setting when Pr. 00-25 is properly set and
Pr.00-26 is not 0.
User-Defined Value
Settings
 Pr. 00-27 displays the user-defined value when Pr. 00-26 is not set to 0.
 The user-defined function is valid only when Pr. 00-20 (frequency source) is set to digital keypad
or RS-485 communication.
LOCAL / REMOTE Mode
Settings
 The default of Pr. 00-29 is 0 (standard Hand-Off-Auto function). Set the AUTO frequency and
operation source with Pr.00-20 and Pr.00-21. Set the HAND frequency and operation source with
Pr.00-30 and Pr.00-31. Select or switch AUTO / HAND mode by using the digital keypad
(KPC-CC01) or setting the multi-function input terminal MI = 41, 42.
 When you set the external terminal (MI) to 41 and 42 (AUTO / HAND mode), Pr.00-29 = 1,2,3,4
are disabled. The external terminal has the highest command priority, and Pr. 00-29 functions in
standard HOA mode.
 When you do not set Pr.00-29 to 0, the Local / Remote function is enabled, and the top right
corner of digital keypad KPC-CC01 (optional) displays LOC or REM (the display is available
0: Disable
0–65535 (when Pr. 00-25 set to no decimal place)
0.0–6553.5 (when Pr. 00-25 set to 1 decimal place)
0.00–655.35 (when Pr. 00-25 set to 2 decimal places)
0.000–65.535 (when Pr. 00-25 set to 3 decimal places)
Read only
0: Standard HOA function
1: When switching between local and remote, the drive stops
2: When switching between local and remote, the drive runs with REMOTE
settings for frequency and operation status
3: When switching between local and remote, the drive runs with LOCAL
settings for frequency and operation status
4: When switching between local and remote, the drive runs with LOCAL
setting when switched to Local and runs with REMOTE settings when
switched to Remote for frequency and operation status.
12.1-00-17
Chapter 12 Description of Parameter SettingsC2000
Default: Read only
Default: 0