Settings
Functions
41
Multi-position reached
42
Crane Function
Actual motor speed
43
higher than Pr. 02-47
44
Low Current Output
UVW output
45
electromagnetic valve
switch
Chapter 12 Description of Parameter SettingsC2000
User can set any three multi-function input terminals to 41. The
current position action status of these three terminals will be
outputted. Example: if setting Pr. 02-36~02-38 to 41 and only the
multi-position of the second point has been done. Then, the
current status is RA (ON), RA (OFF) and MO1 (OFF). In this way,
their status is 010. bit0 is RA and so on.
MO2
Pr.02-17=41
Pr. 04-16
0
Pr. 04-18
0
Pr. 04-20
0
Pr. 04-22
0
Pr. 04-24
0
Pr. 04-26
0
Pr. 04-28
0
Pr. 04-30
1
Pr. 04-32
1
Pr. 04-34
1
Pr. 04-36
1
Pr. 04-38
1
Pr. 04-40
1
Pr. 04-42
1
Pr. 04-44
1
Use this function with Pr. 02-32, Pr. 02-33, Pr. 02-34, Pr. 02-57
and Pr. 02-58.
The example of the crane application is in the following for your
reference.
Active when motor actual speed is higher than Pr. 02-47.
Use this function with Pr. 06-71–Pr. 06-73
Use this function with external terminal input = 49 (drive enabled)
and external terminal output = 45 (electromagnetic valve
enabled), and then the electromagnetic valve is ON or OFF
according to the status of the drive.
12.1-02-15
Descriptions
MO1
RY2
Pr.02-16=41
Pr.02-14=41
0
0
0
1
0
1
1
0
1
0
1
1
1
1
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
RY1
Pr.02-13=41
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1