Chapter 12 Description of Parameter SettingsC2000
Preliminary Counting Value Reached (does not return to 0)
Settings
 When the counter value counts from 1 and reaches this value, the corresponding multi-function
output terminal will be activated, provided one of Pr. 02-13, Pr. 02-14, Pr. 02-36, Pr. 02-37 set to
17 (Preliminary Count Value Setting). This parameter can be used for the end of the counting to
make the drive runs from the low speed to stop.
Digital Output Gain(DFM)
Settings
 It is used to set the signal for the digital output terminals (DFM-DCM) and digital frequency output
(pulse X work period=50%). Output pulse per second = output frequency X Pr. 02-21.
Desired Frequency Reached 1
Settings
The Width of the Desired Frequency Attained 1
Settings
Desired Frequency Reached 2
Settings
The Width of the Desired Frequency Reached 2
Settings
 Once output frequency reaches desired frequency and the corresponding multi-function output
terminal is set to 3 or 4 (Pr. 02-13, Pr. 02-14, Pr. 02-36 and Pr. 02-37), this multi-function output
terminal will be ON.
0~65500
1~166
0.00~599.00Hz
0.00~599.00Hz
0.00~599.00Hz
0.00~599.00Hz
12.1-02-20
Default Setting: 0
Default: 1
Default: 60.00/50.00
Default: 2.00
Default:: 60.00/50.00
Default: 2.00