Input Function Parameters - Delta VFD-EL-W Series Manual

Sensorless vector control compact drive
Hide thumbs Also See for VFD-EL-W Series:
Table of Contents

Advertisement

Chapter 4 Parameters|VFD-EL-W

04 Input Function Parameters

Pr.
04.00 Keypad Potentiometer Bias
Keypad Potentiometer Bias
04.01
Direction
04.02 Keypad Potentiometer Gain
Keypad Potentiometer Negative
04.03
Bias with Reverse Motion
MI Terminal Start/ Stop Method and
04.04
Multi-Function Input Selection
04.05 Reserved
Start/ Stop or Multi-Function Input
04.06
Command 1 (MI2)
Start/ Stop or Multi-Function Input
04.07
Command 2 (MI3)
Multi-Function Input Command 3
04.08
(MI4)
Parameter Name
 You can set this parameter during operation.
Setting Range
0.0–100.0%
0: Positive bias
1: Negative bias
0.1–200.0%
0: Positive bias only
1: Negative bias with reverse command
Mode 1 (Pr.04.19 = 0)
0: MI1 activates (FWD) / Stop
Mode 2 (Pr.04.19 = 1)
0: Two-wire (1) MI1, MI2
1: Two-wire (2) MI1, MI2
3: Three-wire MI1, MI2 and MI3
0: No function
1: Multi-step speed command 1
2: Multi-step speed command 2
3: Multi-step speed command 3
4: Reserved
5: Reset
6: Acceleration / deceleration speed inhibit
7: 1st and 2nd acceleration / deceleration
time selection
8: JOG operation
9: External B.B. input
10: Frequency up command
11: Frequency down command
12: Counter triggered signal input
13: Clear the counter
14: E.F. external fault
15: Disable PID function
16: Output stop
17: Parameter lock
18: Operation command selection: External
terminals
19: Operation command selection: Digital
keypad
20: Operation command selection:
Communication control
21: FWD / REV
48
Default
0.0
0
100.0
0
0
1
2
3