Delta C2000 Series User Manual page 631

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Chapter 13 Warning CodesC2000
ID No.
Display on LCM Keypad
8
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
Add new parameters to the new
firmware version.
Malfunction caused by interference
ID No.
Display on LCM Keypad
9
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
Check if the ambient temperature
or temperature inside the cabinet
is too high, or if there is obstruction
in the ventilation hole of the control
cabinet.
Check if there is any obstruction on
the heat sink or if the fan is running
Insufficient ventilation space
Check if the drive matches the
corresponded loading
The drive has run 100% or more of
the rated output for a long time
Warning Name
Save error 2
Keypad COPY error 2: parameter writing error
(SE2)
Action and Reset
"SE2" warning occurs when writing the parameters incorrectly at the time you
copy parameters to the drive. For example, you copy the new firmware version
with added parameters to the drive with old firmware version.
N/A
N/A
Manual reset
Immediately reset
N/A
SE2: In this stage, the copied data has been transmitted to the Slave.
The Slave compares and processes the copied data, and then saves the data to
the Data ROM. During the process, the data error (should be attribution error)
may occur, or the data cannot be saved to EEPROM. At this time, the warning
occurs.
It is suggested to check the status of Data ROM and remove the error causes
first.
If you cannot clear the error, please contact Delta.
Verify the wiring and grounding of the main circuit, control circuit and the
encoder for effective anti-interference performance.
Warning Name
The AC motor drive detects over-heating of IGBT, and
IGBT over-heating
over the protection level of oH1 warning. (When Pr.
warning (oH1)
06-15 is higher than the IGBT over-heating level, the
drive shows oH1 error without displaying oH1 warning.)
Action and Reset
Pr. 06-15
"oH1" warning occurs when IGBT temperature is higher than Pr. 06-15 setting
value.
N/A
Auto-reset
The drive auto-resets when IGBT temperature is lower than oH1 warning level
minus (–) 5°C
N/A
1. Check the ambient temperature.
2. Regularly inspect the ventilation hole of the control cabinet.
3. Change the installed place if there are heating objects, such as braking
resistors, in the surroundings.
4. Install/ add cooling fan or air conditioner to lower the temperature inside the
cabinet.
Remove the obstruction or replace the cooling fan.
Increase ventilation space of the drive.
1. Decrease loading.
2. Decrease the carrier.
3. Replace with a drive with larger capacity.
Replace with a drive with larger capacity.
13-4
Description
Corrective Actions
Description
Corrective Actions