Delta C2000 Series User Manual page 340

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Pr.
Parameter Name
Parameter protection password
00-08
setting
00-10
Control mode
00-11
Speed control mode
00-12
Point-to-point position mode
00-13
Torque mode control
00-16
Load selection
00-17
Carrier frequency
Chapter 11 Summary of Parameter SettingsC2000
Setting Range
0–65535
0: No password protection / password entered
correctly (Pr. 00-07)
1: Parameter set
0: Speed mode
1: Point-to-point position control mode
2: Torque mode
3: Homing mode
0: IMVF (IM V/F control)
1: IMVFPG (IM V/F control + Encoder)
2: IM/PM SVC (IM / PM space vector control)
3: IMFOCPG (IM FOC + Encoder)
4: PMFOCPG (PM FOC + Encoder)
5: IMFOC sensorless (IM FOC sensorless )
6: PM sensorless (PM FOC sensorless)
7: IPM sensorless (Interior PM FOC sensorless)
0: Relative position
1: Absolute position
0: IM TQCPG (IM torque control + Encoder)
1: PM TQCPG (PM torque control + Encoder)
2: IM TQC sensorless (IM sensorless torque control)
0: Normal load
1: Heavy load
Normal load
VF, VFPG,
PMFOCPG,
SVC,
230V/460V
IMFOCPG,
PMTQCPG
IMTQCPG
1–15HP
2–15kHz
20–50HP
2–10kHz
60–125HP
2–9kHz
Heavy load
VF, VFPG,
PMFOCPG,
SVC,
230V/460V
IMFOCPG,
PMTQCPG
IMTQCPG
1–15HP
2–15kHz
20–50HP
2–10kHz
60–125HP
2–9kHz
575V/690V (Light/ Normal/ Heavy load)
Power/ Control mode
1–15HP (575V)
20–600HP (690V)
850HP (690V)
11-5
PMFOC,
IMFOC,
IPMFOC
IMTQC
4–15kHz
4–10kHz
4–14kHz
4–10kHz
4–10kHz
4–10kHz
4–9kHz
4–9kHz
4–9kHz
PMFOC,
IMFOC,
IPMFOC
IMTQC
4–15kHz
4–10kHz
4–14kHz
4–10kHz
4–10kHz
4–10kHz
4–9kHz
4–9kHz
4–9kHz
VF, VFPG, SVC
2–15kHz
2–9kHz
2–9kHz
Default
0
0
0
0
0
0
8
6
4
2
6
4
3

Hide quick links:

Advertisement

Table of Contents
loading