Chapter 16 PLC Function ApplicationsC2000
API
CMP
10
D
Bit device
X
Y
M
S1
S2
D
*
*
Notes on operand usage:
The operand D occupies three consecutive points
Compares the size of the content of operand
comparison are expressed in
Size comparison is performed algebraically. All data is compared in the form of
numerical binary values. Because this is a 16-bit command, when b15 is 1, this
indicates a negative number.
When the designated device is Y0, it automatically occupies Y0, Y1 and Y2.
When X10=On, the CMP command executes, and Y0, Y1 or Y2 will be On. When
X10=Off, the CMP command will not execute, and the state of Y0, Y1 and Y2 will
remain in the state prior to X10=Off.
If ≥, ≤, or ≠ results are needed, they can be obtained via series/parallel
connections of Y0–Y2.
To clear results of comparison, use the RST or ZRST command.
S1
S2
D
P
Word device
K
H
KnX KnY KnM
*
*
*
*
*
*
*
*
*
*
S1
: Compare value 1.
X10
RST
RST
RST
Compares set output
16-bit command (7 STEP)
CMP
T
C
D
*
*
*
*
*
*
32-bit command (13 STEP)
DCMP
Flag signal: none
S2
: Compare value 2.
D
.
X10
M0
M1
M2
16-56
Continuous
CMPP
execution type
execution type
Continuous
DCMPP
execution type
execution type
D
: Results of comparison.
S1
S2
and
; the results of
ZRST
M0
M2
Pulse
Pulse

Hide quick links: