Delta C2000 Series User Manual page 376

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Pr.
Parameter Name
08-18
Sleep mode function setting
08-19
Wake-up integral limit
08-20
PID mode selection
Enable PID to change the
08-21
operation direction
08-22
Wake-up delay time
08-23
PID control flag
Chapter 11 Summary of Parameter SettingsC2000
Setting Range
0: Refer to PID output command
1: Refer to PID feedback signal
0.0–200.0%
0: Serial connection
1: Parallel connection
0: Operation direction cannot be changed
1: Operation direction can be changed
0.00–600.00 sec.
bit0 = 1, PID running in reverse follows the setting for
Pr. 00-23.
bit0 = 0, PID running in reverse follows PID's calculated
value.
bit1 = 1, second decimal place of PID Kp
bit1 = 0, first decimal place of PID Kp
11-41
Default
0
50.0
0
0
0.00
0000h