Delta C2000 Series User Manual page 289

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Chapter 9 Specification C2000
9-5 Environment for Operation, Storage and Transportation
DO NOT expose the AC motor drive in the bad environment, such as dust, direct sunlight, corrosive / inflammable gasses,
humidity, liquid and vibration environment. The salt in the air must be less than 0.01mg / cm
Installation
location
Surrounding
Temperature
(°C)
Rated Humidity
Air Pressure
(kPa)
Environment
Pollution Level
Altitude
Storage
Package Drop
Transportation
1.0mm, peak to peak value range from 2Hz to 13.2 Hz; 0.7G~1.0G range from 13.2Hz to 55Hz; 1.0G range
Vibration
from 55Hz to 512Hz. Comply with IEC 60068-2-6
Impact
IEC / EN 60068-2-27
Max. allowed offset angle 10
Operation
Position
installation position)
IEC60364-1 / IEC60664-1 Pollution degree 2, Indoor use only
Storage /
-25 ~ +70
Transportation
Non-condensation, non-frozen
Operation
Max. 95%
Storage /
Max. 95%
Transportation
No condense water
Operation /
86~106
Storage
Transportation
70~106
IEC 60721-3-3
Operation
Class 3C3; Class 3S2
Storage
Class 1C2; Class 1S2
Transportation
Class 2C2; Class 2S2
If the AC motor drive is to be used under harsh environment with high level of contamination
(e.g. dew, water, dust), make sure it is installed in an environment qualified for IP54 such as in
a cabinet.
If AC motor drive is installed at altitude 0~1000m, follow normal operation
restriction. If it is installed at altitude 1000~2000m, decrease 1% of rated
Operation
current or lower 0.5°C of temperature for every 100m increase in altitude.
Maximum altitude for Corner Grounded is 2000m.
ISTA procedure 1A (according to weight) IEC60068-2-31
o
(under normal
10
10
9-10
every year.
2
Table 9-8